Sensorclouds
Step-by-Step Guides

Setting Up Alarms

Create alarms that catch real problems without flooding your team, and test them end to end

ADMIN ENGINEER

Good alarms are rare, clear, and actionable. This guide sets up a cold-room alarm, routes it to the right people, and tests it.

What you'll need

  • A device sending temperature
  • Optionally, a Slack or Telegram integration

Step 1: Decide what's worth an alarm

FieldConditionSeverityWhy
temperature> 8 °C for 2 minutesCRITICALProduct spoils
temperature> 6 °C for 5 minutesWARNINGEarly warning
battery< 20%WARNINGPlan a battery swap

For each alarm, write down who acts and what they do. If nobody would act, it shouldn't be an alarm.

Step 2: Create the CRITICAL rule

Open the application, then Alarms (Alarm Configurations), and click Add Alarm Configuration.

Fill in:

FieldValue
Alarm NameCold room above 8 °C
DescriptionCheck the door seal and compressor. Call facilities if it's still rising
DeviceAll Devices
Field / Operator / Thresholdtemperature / > / 8
SeverityCRITICAL
Duration (seconds)120
Cooldown (minutes)30
ActionsIn-App Notification, plus Webhook Integration with your Slack or Telegram integration

Click Create Alarm.

Step 3: Add the WARNING rule

The same as above, with threshold 6, duration 300, cooldown 60, severity WARNING, and In-App Notification only.

Step 4: Test it

Send a reading above 8, for example with the quick test. With a 120-second duration, send it twice, more than 2 minutes apart (or temporarily set the duration to 0).

Check:

  • The Alarms page (main sidebar) shows an ACTIVE alarm on the Active tab
  • The bell shows a notification
  • Your Slack or Telegram channel got a message

Send a reading below 8. The alarm resolves itself and an Alarm resolved notification follows.

Step 5: Handle it like a real alarm

Open the alarm and click Acknowledge to show your team you're on it.

When the cause is fixed, the alarm resolves automatically, or click Resolve.

Step 6: Tune after a week

Look at Alarms → History:

You seeChange
Fires many times a dayRaise the threshold, or lengthen the duration
Fires and clears within secondsLengthen the duration
One incident produces many alarmsLengthen the cooldown
Never fires, but problems happenedLower the threshold

Next Steps

On this page