Setting Up Alarms
Create alarms that catch real problems without flooding your team, and test them end to end
Good alarms are rare, clear, and actionable. This guide sets up a cold-room alarm, routes it to the right people, and tests it.
What you'll need
- A device sending
temperature - Optionally, a Slack or Telegram integration
Step 1: Decide what's worth an alarm
| Field | Condition | Severity | Why |
|---|---|---|---|
temperature | > 8 °C for 2 minutes | CRITICAL | Product spoils |
temperature | > 6 °C for 5 minutes | WARNING | Early warning |
battery | < 20% | WARNING | Plan a battery swap |
For each alarm, write down who acts and what they do. If nobody would act, it shouldn't be an alarm.
Step 2: Create the CRITICAL rule
Open the application, then Alarms (Alarm Configurations), and click Add Alarm Configuration.
Fill in:
| Field | Value |
|---|---|
| Alarm Name | Cold room above 8 °C |
| Description | Check the door seal and compressor. Call facilities if it's still rising |
| Device | All Devices |
| Field / Operator / Threshold | temperature / > / 8 |
| Severity | CRITICAL |
| Duration (seconds) | 120 |
| Cooldown (minutes) | 30 |
| Actions | In-App Notification, plus Webhook Integration with your Slack or Telegram integration |
Click Create Alarm.
Step 3: Add the WARNING rule
The same as above, with threshold 6, duration 300, cooldown 60, severity WARNING, and
In-App Notification only.
Step 4: Test it
Send a reading above 8, for example with the quick test. With a 120-second duration, send it twice, more than 2 minutes apart (or temporarily set the duration to 0).
Check:
- The Alarms page (main sidebar) shows an ACTIVE alarm on the Active tab
- The bell shows a notification
- Your Slack or Telegram channel got a message
Send a reading below 8. The alarm resolves itself and an Alarm resolved notification follows.
Step 5: Handle it like a real alarm
Open the alarm and click Acknowledge to show your team you're on it.
When the cause is fixed, the alarm resolves automatically, or click Resolve.
Step 6: Tune after a week
Look at Alarms → History:
| You see | Change |
|---|---|
| Fires many times a day | Raise the threshold, or lengthen the duration |
| Fires and clears within seconds | Lengthen the duration |
| One incident produces many alarms | Lengthen the cooldown |
| Never fires, but problems happened | Lower the threshold |